HTemp-485, Luftfeuchtigkeits, Temperatur Sensor / Sensoren, Luftfeuchtigkeitssensor, Luftfeuchtigkeitsseensoren, Temperatursensor, Temperatursensoren, Temperature probe, Humidity probe
|
| |
|
|
|
|
| |
Combined temperature and humidity sensor for vertical wall mounting indoor usage. Communication over RS-485 bus with a simple communication protocol. The sensor can be used separately but it was designed to be connected with the Poseidon family units.
HTemp-485 measures temperature and humidity. The sensor is intended for indoor vertical wall mounting.
HTemp-485 measures temperature and humidity, communicates over 4-wire bus and up to 26 sensors can be connected parallely to a single bus. The sensor is intended for indoor vertical wall mounting.
The busbar uses 4 wires, two with a standard RS-485 line, the other two are used for sensors' power supply. The individual sensors can be powered by an external power source and can be connected by just two RS-485 line wires. RS-485 communication line works up to 1000m distance.
For temperature measuring the thermal sensor uses an integrated element with accuracy of ±0.5°C, humidity is as well measured by an external sensor with accuracy ±4%. The HTemp-485 module contains an indicator, signalizing by blinking that temperature (green) or humidity (orange) measuring is in progress.
Application
* Extensive measuring systems with many measuring points
* Climatization state measuring and measuring of living conditions in intelligent buildings
* Independent measuring in food warehouses and agricultural crops storage buildings
* Grocery storehouses and premises, hard measuring conditions
* Thermal and humidity monitoring in pharmaceutical storages
* Measuring in residential premises
* Industrial measuring and regulation
* After connection to the Poseidon – temperature transmission over Ethernet or Internet
* After connection to the Poseidon – possible logging of up to 100 000 values into internal Flash memory
Basic properties
* Temperature measuring within the range of -10°C to +80°C
* Measuring the relative humidity within the range of 0% to 100%.
* Up to 25 sensors connected parallely at one bus
* Communication and sensor state indication
* Communication over the RS-485 line (up to 1 000 m distance), simple communication protocol
* Minimal power consumption, possible power supply by unstabilized voltage
* The sensor by itself can send a temperature value according to preset time interval, which can be from 1 to 5000 seconds (circa 1 hour and 23 minutes)
* The sensor address on RS-485 bus can be set by jumpers inside the sensor as well
* Easy wall mounting, connection conductors can be led along the wall in molding or from below of the installation box.
* The sensor cooperates with SNMP thermometer Poseidon
|
| |
| |
|
|
Ansprechperson |
DANKE das SIE uns besuchen.
Günther Lugauer
Beratung & Verkauf
guenther.lugauer[a]bellequip.at
Tel: +43 (0) 2822 33 33 996
Mobil: +43 (0) 664 33 33 996
BellEquip Zentrale:
Tel: +43 (0) 2822 33 33 990
Fax: +43 (0) 2822 33 33 995
info[a]bellequip.at
Rack Monitoring
Remote Power Management
Secure Console Server
Device Server
Terminal Server
Serielle Lösungen
Datenkommunikation
Netzwerktechnik
GSM / GPRS / EDGE
UMTS / HSDPA
Wireless Communication
|
|